Overview
» get the Agent » PSsystec Downloads
Smartbox, based on the Telit Chipset xE910 is a ready to use solution for connecting to Profibus Networks to the Cumulocity IoT Cloud. It provides a Profibus Slave Communication on DPV0 Standard as well as 2 Sensorinputs and a Modbus RTU Master Communication. Easy configure the SetUp the S7 PLC Data Echange to the box. Using the MQTT protocol the terminal comes up with a low traffic solution
Datasheet
Radio
Radio | |
---|---|
4G LTE | |
3G | |
2G | GSM | GPRS |
Regions | EMEA / APAC / Latinamerica / NorthAmerica / Australia / Global (3G / 2G) |
GPS | Supported by 2G and 3G Variances |
Production | The selected Region,Technology and GPS can be defined during Production. The default assembly is 3G with supported regions EMEA / APAC |
Connectivity/ Features
Connectivity/ Features | ||||
---|---|---|---|---|
Layout | ||||
Fieldbus Profibus | Type | Profibus Slave | ||
Standard | DP-V0 | |||
Baudrate | Automatic Baudrate Detection Supported Baudrates: |9,6kbit | 19,2kbit | 45,45kbit | 93,75kbit | 187,5kbit | 500kbit | 1500kbit | 3000kbit | 6000kbit | 12000kbit | |||
GSD File | ID Number : 1023 HEX GSD file : PSYS1023.GSD | |||
Input Register | 16 (16bit) | |||
Output Register | 16 (16bit) | |||
Profibus Slave address | Selectable by Cloud, Default: 24 | |||
ASIC | VPC3+S (Profichip) | |||
Fieldbus Modbus | Type | Modbus RTU Master | ||
Baudrate | 4800, 9600, 19200, 38400, 57600, 115200 | |||
Parity | Even, ODD, NONE | |||
Stoppbits | 2,1 | |||
Functioncodes | ||||
Datapoints | Max. 10 Modbus Slaves, with 100 datapoints per device or 1000 datapoints with 1 device | |||
Sensors | 2 Sensor Inputs | |||
DIN/O | DIN [voltage free] | |||
AIN | NTC | 0..20mA (selectable by Hardware) | |||
LEDs | GSM | Flashing- connected to mobile network | ||
RUN | 2xflashing/pause: StartUp Phase 3xflashing/pause: Connected to Server, Data exchange | |||
Act | Flashing: Sensor Board Power | |||
Link | Flashing: Sensor Board is ready to process data | |||
USB | For programming, Logging and Trace the device |
Cloud Connector
Cloud Connector | ||||
---|---|---|---|---|
Availability | All Cumulocity Based systems, Cloud der Dinge Deutsche Telekom | |||
Realtime Clock | Updating Realtime automatical from #NTP timeserver | |||
Application | CloudFieldbus (CFB Integrated in Devicemanagement)For SetUp connected field devices | |||
Online Operations | Remote Restart Fieldbus Configuration Cloud-Device Change Transmitinterval from device to Cloud Change Communication. Baudrate, Databits, Parity, Stopbits Operate the connected Field device: Registervalues (R/W) Operate the connected Field device: Change CoilValues (R/W) Operate the device with AT Commands in the shell | |||
Communication | MQTT | |||
Security | TLS-Security 1.0 / TLS 1.2 (ab Version 2.4.x) | |||
Notifications | Realtime and Pending Operations | |||
Shell | Operate the device with AT Commands in the shell | |||
Location | Identification by cellular network or GPS Signal (selected- see Radio) | |||
Tracking | Location Route by cellular network or GPS Signal | |||
Info | Operator, Cell ID, LAC, MNC, MCC, Signal strength | |||
Device Database | Device database Support for Modbus and Profibus: Measurements, Event, Alarms, Values, Read, Read/Write, Signed/Unsigned, Decimal Places, Multiplier, Divisor, No of Bits, StartBit | |||
OTA | RemoteUpdate Software | |||
Data-Exchange | Values | On Change | ||
Alarms | On Change | |||
Events | On Change | |||
Measurements | Default 900 | |||
Signal strength | Is sent every 20 Min as a measurement | |||
Offline Buffering | Alarms, Events, Measurments ≈ 72h | |||
SMS | For Troubleshooting you can operate the device by SMS:RebootChange tenantFOTA/OTA |
General
General | |
---|---|
Dimensions | 100 x 70 x 45 mm |
Weight | 89g |
GSM Antenna | SMA Connector |
Power Supply | Nominal voltage range: 12-24 VDC, 10% Maximum continuous (average) supply power: 2.5 W Maximum continuous (average) supply current: 200 mA at 12V, 100 mA at 24V |
Mounting | Via DIN Rail Adapter or Adapter for Wall Mounting |
SIM Card Format | 2FF |
Operating temperature | -20..60°C |
Storage temperature | -40..85°C |
Operating humidity | Max. 85% |
Storage humidity | Max. 85% |
IP Class | IP20/IP54 (opt.) |
Approvals | |
Conformity Declerations | 2014/53/EU (Radio Equipment Directive - RED)RadioEN301511 v12.5.1 for GSM 900 and 1800 MHzEN301908 v11.1.1 for UMTS band 1 and 8EMCEN 301489-1 v2.1.1 general partEN 301489-52 v0.0.7 for GSM and UMTSSafetyEN60950-01 |
Profibus Organisation | ID Number : 1023 HEX GSD file : PSYS1023.GSD |